Typical power cables
US
2)
IEC
1)
ACS880-
04F-…
Al cable type
Cu cable type
Al cable type
Cu cable type
AWG/kcmil
AWG/kcmil
mm
2
mm
2
U
n
= 400 V
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×150)
3×(3×95)
504A-3
3×400 MCM or 4×250 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×120)
584A-3
3×400 MCM or 4×250 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
649A-3
3×500 MCM or 4×300 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
725A-3
3×700 MCM or 4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
820A-3
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
880A-3
U
n
= 500 V
2×600 MCM or 3×300 MCM
2×400 MCM or 3×4/0
3×(3×150)
3×(3×95)
459A-5
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×150)
3×(3×95)
502A-5
3×500 MCM or 4×300 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×120)
582A-5
3×600 MCM or 4×400 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
6354-5
3×600 MCM or 4×400 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
715A-5
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
820A-5
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
880A-5
U
n
= 690 V
2×350 MCM or 3×4/0
2×250 MCM or 3×2/0
3×(3×120)
2×(3×120)
329A-7
2×400 MCM or 3×4/0
2×300 MCM or 3×3/0
3×(3×120)
2×(3×120)
369A-7
2×500 MCM or 3×250 MCM
2×350 MCM or 3×4/0
2×(3×120)
2×(3×95)
429A-7
2×600 MCM or 3×300 MCM
2×400 MCM or 3×4/0
3×(3×150)
3×(3×95)
470A-7
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×185)
3×(3×120)
522A-7
3×500 MCM or 4×300 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×150)
590A-7
3×500 MCM or 4×300 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
650A-7
3×600 MCM or 4×400 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
721A-7
1) The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
2) The cable selection is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible temperature of con-
ductor in continuous use. For North America, power cables must be rated for 75 °C (167 °F) or higher.
Voltage: 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for up to 600 V AC.
1000 V AC cable is accepted for up to 690 V AC.
Terminal and entry data for the power cables
4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM)
Maximum accepted
cable size
26 Technical data and references