Electrical installation 79
using a measuring voltage of 1 kV DC. The insulation resistance must be higher than
1 Mohm.
Checking the compatibility with IT (ungrounded) systems
EMC E200 is not suitable for use in an IT (ungrounded) system. If the drive is
equipped with E200, disconnect the filter grounding wire before connecting the drive
to the supply network. Insulate the end of the wire and attach it. The wire is located behind
the middle front cover.
WARNING!
If a drive with EMC E200 is installed on an IT system (an
ungrounded power system or a high resistance-grounded [over 30 ohm] power
system), the system will be connected to earth potential through the EMC filter
capacitors of the drive. This can cause danger, or damage the drive.
ohm
R-
R+
PE
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...