156 Safe torque off function
Single-channel connection
Notes
:
• Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL classification
is given.
• Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded cable.
For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4
+24 V
OUT1
SGND
IN2
K
IN1
ACS880-04F
Control unit