126 Technical data
Note 1:
Implementing thermal overload and short-circuit protection
on page
Note 2:
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Fuses with higher current rating than the recommended ones must not be used. Fuses with lower
current rating can be used.
Note 4:
Fuses from other manufacturers can be used if they agree with the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
Dimensions, weights and free space requirements
1 Height of standard drive module with hood: 1930 mm (75.98 in)
2 Depth of standard drive module with hood: 556 mm (21.89 in)
3 Height with optional sel0B051+0H371, flange (or wall mounting kit) and hood: 1877 mm (73.90 in).
4 Depth with optional sel0B051+0H371 and hood: 479 mm (18.87 in)
5 Height with optional sel0B051+0H371 and hood, but without flange: 1755 mm (69.09 in). The
height is the same with the wall mounting kit instead of flange.
For requirements of free space around the drive module, see page
.
715A-5
715
800
600
Ferraz
L
A4BY800
820A-5
820
900
600
Ferraz
L
A4BY900
880A-5
880
1000
600
Ferraz
L
A4BY1000
Standard drive module configuration (including flange and shrouds)
Frame
size
Height
1)
Width
Depth
2)
Weight
mm
in
mm
in
mm
in
kg
lb
R11
1733
68.23
620
24.41
477
18.78
224
494
Optional sel0B051+0H371 (without shrouds, full-size output power cable connection
terminals but with flange)
Frame
size
Height
3)
Width
Depth
4)
Weight
mm
in
mm
in
mm
in
kg
lb
R11
1647
64.84
620
24.41
405
15.94
219
483
Optional sel0B051+0H371 (without shrouds, full-size output power cable connection
terminals and flange)
Frame
size
Height
5)
Width
Depth
4)
Weight
mm
in
mm
in
mm
in
kg
lb
R11
1525
60.05
535
21.06
405
15.94
219
483
Optional sel0B051+E208+0H371+C217 (without shrouds, full-size output power cable
connection terminals and with wall mounting kit instead of flange)
Frame
size
Height
3)
Width
Depth
4)
Weight
mm
in
mm
in
mm
in
kg
lb
R11
1647
64.84
620
24.41
405
15.94
222
489
Weight of optional selections
Frame
size
+E208
+D150
+H356
+0H371
+H370
+0B051
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
R11
3
7
9
20
2
4
-2.9
-6
2.9
6
-1.5
-3
Drive type
ACS880-04F-
Input
current
(A)
Fuse
A
V
Manufacturer
UL class
Type
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...