122 Technical data
Altitude derating
At altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for
every 100 m (328 ft). If ambient temperature is below +40 °C (+104 .°F), the derating can
be reduced by 1.5% for every 1 °C reduction in temperature. For a more accurate
derating, use the DriveSize PC tool. A few altitude derating curves are shown below.
Deratings for special settings in the drive control program
Enabling special settings in the drive control program can require output current derating.
Ex motor, sine filter, low noise
Table below gives the deratings for these cases:
•
drive is used with an ABB motor for explosive atmospheres (Ex) and
EX motor
in
Parameter
95.15 Special HW settings
is enabled
•
sine filter given in the selection table on page
is used and
ABB sine filter
in
Parameter 95.15 Special HW settings
is enabled
•
Low noise optimization
is selected in
Parameter 97.09 Switching freq mode
.
Derating factor 1.00
Derating factor 0.95
Derating factor 0.9
Derating factor 0.85
Derating factor 0.80
1500 m
1000 m
+25 °C
+30 °C
+77 °F
+86 °F
Ambient temperature
+40 °C
+104 °F
+35 °C
+95 °F
+20 °C
+68 °F
3300 ft
4921 ft
2000 m
6562 ft
2500 m
8202 ft
3000 m
9842 ft
3500 m
11429 ft
4000 m
13123 ft
Installation site altitude
1.00
0.95
0.85
0.90
0.80
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...