Technical data 121
Ambient temperature derating
In the temperature range +40…55 °C (+104…131 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F) as follows. Calculate the output current by multiplying
the current given in the rating table by the derating factor.
1.00
0.85
+40 °C
+55 °C
+104 °F
+131 °F
Derating factor
Ambient temperature