1.
Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2.
If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, make sure that the connection steps are low enough
not to cause voltage transients that would trip the drive.
3.
Make sure that the power factor compensation unit is suitable for use in systems
with AC drives, ie, harmonic generating loads. In such systems, the compensation
unit should typically be equipped with a blocking reactor or harmonic filter.
Using a safety switch between the drive and the motor
ABB recommends to install a safety switch between the permanent magnet motor
and the drive output. The switch is needed to isolate the motor from the drive during
maintenance work on the drive.
Implementing an ATEX-certified motor thermal protection
With Q971, the drive provides ATEX-certified safe motor disconnection without
contactor using the drive Safe torque off function. To implement the thermal protection
of a motor in explosive atmosphere (Ex motor), you must also:
•
use an ATEX-certified Ex motor
•
order an ATEX-certified thermistor protection module for the drive (L537),
or acquire and install an ATEX-compliant protection relay
•
do the necessary connections.
For more information, see:
Manual code
(English)
User's manual
ATEX-certified Safe disconnection function, Ex II (2) GD for ACS880 drives (+Q971)
application guide
FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option
+L537+Q971) for ACS880 drives user's manual
Implementing the power loss ride-through function
If the incoming supply voltage is cut off, the drive will continue to operate by utilizing
the kinetic energy of the rotating motor. The drive will be fully operational as long as
the motor rotates and generates energy to the drive.
If you equip the drive with a main contactor or breaker, make sure that it restores the
drive input power after a short break. The contactor must either re-connect after the
break automatically, or remain closed over the break. Depending on the contactor
control circuit design, this can require an additional hold circuit, uninterruptible auxiliary
power supply or auxiliary power supply buffering.
Note: If the power loss lasts so long that the drive trips on undervoltage, a fault reset
and a fresh start command is required to continue operation.
Implement the power-loss ride-through function as follows:
Guidelines for planning the electrical installation 79
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...