If motor power is below 350 kW: Equip the drive and/or motor with the filters
and/or bearings according to the table below.
•
If motor power is above 350 kW: Consult the motor manufacturer.
Requirement for
Nominal AC supply
voltage
ABB d
u/dt and common mode filters, insulated N-
end motor bearings
Motor insulation system
100 kW <
P
n
< 350 kW or
IEC 315 < frame size < IEC
400
P
n
< 100 kW or frame size
< IEC 315
134 hp <
P
n
< 469 hp or
NEMA 500 < frame size <
NEMA 580
P
n
< 134 hp or frame size
< NEMA 500
+ N or CMF
+ N or CMF
Standard:
Û
LL
= 1300 V
U
n
≤ 420 V
+ N + d
u/dt + CMF
+ d
u/dt + (N or CMF)
Standard:
Û
LL
= 1300 V
420 V <
U
n
< 500 V
or
+ N or CMF
+ N or CMF
Reinforced:
Û
LL
= 1600 V,
0.2 microsecond rise time
+ N + d
u/dt + CMF
+ d
u/dt + (N or CMF)
Reinforced:
Û
LL
= 1600 V
500 V <
U
n
≤ 600 V
or
+ N + CMF
+ N or CMF
Reinforced:
Û
LL
= 1800 V
+ N + d
u/dt + CMF
+ N + d
u/dt
Reinforced:
Û
LL
= 1800 V
600 V <
U
n
≤ 690 V
+ N + CMF
+ N + CMF
Reinforced:
Û
LL
= 2000 V,
0.3 microsecond rise
time
1)
1) If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term resistor
braking cycles, check with the motor manufacturer if additional output filters are needed.
Additional data for calculating the rise time and the peak line-to-line voltage
The diagrams below show the relative peak line-to-line voltage and rate of change of
voltage as a function of the motor cable length. If you need to calculate the actual
peak voltage and voltage rise time considering the actual cable length, proceed as
follows:
•
Peak line-to line voltage: Read the relative
Û
LL
/
U
n
value from the diagram below
and multiply it by the nominal supply voltage (
U
n
).
•
Voltage rise time: Read the relative values
Û
LL
/
U
n
and (d
u/dt)/U
n
from the diagram
below. Multiply the values by the nominal supply voltage (
U
n
) and substitute into
equation t = 0.8 ·
Û
LL
/(d
u/dt).
64 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...