Protecting the motor insulation and bearings
The drive employs modern IGBT inverter technology. Regardless of frequency, the
drive output comprises pulses of approximately the drive DC bus voltage with a very
short rise time. The pulse voltage can almost double at the motor terminals, depending
on the attenuation and reflection properties of the motor cable and the terminals.
This can cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings. This
can gradually erode the bearing races and rolling elements.
d
u/dt filters protect motor insulation system and reduce bearing currents. Common
mode filters mainly reduce bearing currents. Insulated N-end (non-drive end) bearings
protect the motor bearings.
■
Requirements tables
These tables show how to select the motor insulation system and when a drive d
u/dt
and common mode filters and insulated N-end (non-drive end) motor bearings are
required. Ignoring the requirements or improper installation may shorten motor life
or damage the motor bearings and voids the warranty.
Requirements for ABB motors,
P
n
< 100 kW (134 hp)
See also
Requirement for
Nominal AC line
voltage
Motor type
ABB d
u/dt and common mode filters, insulated
N-end motor bearings
Motor insula-
tion system
P
n
< 100 kW and frame size < IEC 315
P
n
< 134 hp and frame size < NEMA 500
-
Standard
U
n
≤ 500 V
Random-wound
M2_, M3_ and M4_
+ d
u/dt
Standard
500 V <
U
n
≤ 600 V
-
Reinforced
+ d
u/dt
Reinforced
600 V <
U
n
≤ 690 V
(cable length ≤
150 m)
-
Reinforced
600 V <
U
n
≤ 690 V
(cable length >
150 m)
N/A
Standard
380 V <
U
n
≤ 690 V
Form-wound HX_
and AM_
+ N + d
u/dt with voltages over 500 V + CMF
Check with
the motor
manufac-
turer.
380 V <
U
n
≤ 690 V
Old
1)
form-wound
HX_ and modular
+ N + CMF
Enamelled
wire with
fiber glass
taping
0 V <
U
n
≤ 500 V
Random-wound HX_
and AM_
2)
+ N + d
u/dt + CMF
500 V <
U
n
≤ 690 V
Consult the motor manufacturer.
HDP
1) manufactured before 1.1.1998
2) For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
Guidelines for planning the electrical installation 59
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...