Fuses (IEC)
aR fuses by Cooper Bussmann for protection against short-circuit in the input power
cable of the drive are listed below.
Ultrarapid (aR) fuses per drive module
Drive type
ACS880-04F-…
Fuse
Input current
Min. short-cir-
cuit current
Size
Type DIN
43653
V
A
2
s
A
A
A
U
n
= 400 V
3
170M6012
690
465000
800
504
4500
504A-3
3
170M6014
690
945000
1000
584
6500
584A-3
3
170M6014
690
945000
1000
649
6500
649A-3
3
170M6016
690
1950000
1250
725
9100
725A-3
3
170M6019
690
3900000
1600
820
11000
820A-3
3
170M6019
690
3900000
1600
880
11000
880A-3
U
n
= 500 V
3
170M6010
690
210000
630
459
3000
459A-5
3
170M6012
690
465000
800
502
4500
502A-5
3
170M6014
690
945000
1000
582
6500
582A-5
3
170M6014
690
945000
1000
634
6500
634A-5
3
170M6016
690
1950000
1250
715
9100
715A-5
3
170M6019
690
3900000
1600
820
11000
820A-5
3
170M6019
690
3900000
1600
880
11000
880A-5
U
n
= 690 V
3
170M6011
690
300000
700
329
3600
329A-7
3
170M6013
690
670000
900
369
5600
369A-7
3
170M6014
690
945000
1000
429
6500
429A-7
3
170M6015
690
1300000
1100
470
7800
470A-7
3
170M6016
690
1950000
1250
522
9100
522A-7
3
170M6017
690
2450000
1400
590
10200
590A-7
3
170M6018
690
3100000
1500
650
10500
650A-7
3
170M6018
690
3100000
1500
721
10500
721A-7
Note: In multicable installations, install only one fuse per phase (not one fuse per
conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Fuses from other manufacturers can be used if they agree with the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
■
Calculating the short-circuit current of the installation
Make sure that the short-circuit current of the installation is at least the value given
in the fuse table.
Technical data 139
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...