Recommended maintenance intervals after start-up
Years from start-up
Component
…
12
11
10
9
8
7
6
5
4
3
2
1
Cooling
R
Main cooling fan
R
Circuit board compartment
cooling fan
R
NSIN filter cooling fan
Batteries
R
Control panel battery
R
R
Control unit battery
Connections and environment
R
R
R
R
R
R
R
R
R
R
R
R
R
Cabinet door filters (IP54)
P
P
P
P
P
P
P
P
P
P
P
P
P
Quality of supply voltage
Spare parts
I
I
I
I
I
I
I
I
I
I
I
I
I
Spare part stock
P
P
P
P
P
P
P
P
P
P
P
P
P
Reforming DC circuit capacitors
(spare modules and spare capa-
citors)
Inspections by user
I
I
I
I
I
I
I
I
I
I
I
I
I
Air inlet and outlet meshes
(IP22/IP42)
I
I
I
I
I
I
I
I
I
I
I
I
I
Tightness of terminals
I
I
I
I
I
I
I
I
I
I
I
I
I
Ambient conditions (dustiness,
moisture, corrosion, temperat-
ure)
I
I
I
I
I
I
I
I
I
I
I
I
I
Cleaning of heatsinks
Funtional safety
I
See the maintenance information of the safety function.
Safety function test
20 years
Safety component expiry (Mis-
sion time,
T
M
)
Note:
•
Maintenance and component replacement intervals are based on the assumption
that the equipment is operated within the specified ratings and ambient
conditions. ABB recommends annual drive inspections to ensure the highest
reliability and optimum performance.
•
Long term operation near the specified maximum ratings or ambient conditions
may require shorter maintenance intervals for certain components. Consult your
local ABB Service representative for additional maintenance recommendations.
118 Maintenance
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...