![ABB ACS880-01 Series Firmware Instructions Download Page 86](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621086.webp)
86 Program features
The function is based on a PI controller. The proportional gain and integration time
can be defined by parameters. Setting these to zero disables rush control.
Settings
Parameters
and
(page
Encoder support
The program supports two single-turn or multiturn encoders (or resolvers). The
following optional interface modules are available:
• TTL encoder interface FEN-01: two TTL inputs, TTL output (for encoder
emulation and echo) and two digital inputs
• Absolute encoder interface FEN-11: absolute encoder input, TTL input, TTL
output (for encoder emulation and echo) and two digital inputs
• Resolver interface FEN-21: resolver input, TTL input, TTL output (for encoder
emulation and echo) and two digital inputs
• HTL encoder interface FEN-31: HTL encoder input, TTL output (for encoder
emulation and echo) and two digital inputs
• HTL/TTL encoder interface FSE-31 (for use with an FSO-xx safety functions
module): Two HTL/TTL encoder inputs (one HTL input supported at the time of
publication).
The interface module is to be installed onto one of the option slots on the drive control
unit. The module (except the FSE-31) can also be installed onto an FEA-03 extension
adapter.
Motor speed
Time
Overspeed trip level
Overspeed trip level
0
Rush control active
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...