Fault tracing 597
7081
Control panel loss
Programmable fault:
Control panel (or PC tool) has
stopped communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows:
0:
Panel,
1:
Fieldbus interface A,
2:
Fieldbus interface B,
3:
Ethernet,
4:
D2D/EFB port).
7082
Ext I/O comm loss
The I/O extension module
types specified by parameters
do not match the detected
configuration.
Check the auxiliary code (format
XXYY YYYY). “XX” specifies the number
of the I/O extension module (
01:
02:
03:
“YY YYYY” indicates the problem (see
actions for each code below).
00 0001 Communication with module
failed.
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
00 0002 Module not found.
Check the type and location settings of
the modules (parameters
/
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
00 0003 Configuration of module failed.
00 0004 Configuration of module failed.
7083
Panel reference
conflict
Use of saved control panel
reference in multiple control
modes attempted.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
7084
Panel/PC tool version
conflict
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
Update control panel and/or PC tool.
Contact your local ABB representative if
necessary.
7085
Incompatible option
module
Option module not supported.
(For example, type Fxxx-xx-M
fieldbus adapter modules are
not supported.)
Check the auxiliary code. The code
specifies the interface to which the
unsupported module is connected:
1:
Fieldbus interface A,
2:
Fieldbus
interface B.
Replace the module with a supported
type.
7121
Motor stall
Programmable fault:
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...