594 Fault tracing
6181
FPGA version
incompatible
Firmware and FPGA file
version in the power unit are
incompatible.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
Update of power unit logic
failed.
Retry.
6200
Checksum mismatch
Programmable fault:
The calculated parameter
checksum does not match any
enabled reference checksum.
See
(page
6306
FBA A mapping file
Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6307
FBA B mapping file
Fieldbus adapter B mapping
file read error.
Contact your local ABB representative.
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A2
Internal record load
Internal record load error.
Contact your local ABB representative.
64A3
Application loading
Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty.
In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all”
command, and reload the application.
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A5
Licensing fault
Running the control program is
prevented either because a
restrictive license exists, or
because a required license is
missing.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...