592 Fault tracing
5093
Rating ID mismatch
The hardware of the drive does
not match the information
stored in the memory unit. This
may occur eg. after a firmware
update or memory unit
replacement.
Cycle the power to the drive.
Check the auxiliary code. The auxiliary
code categories are as follows:
1 = PU and CU ratings not the same.
Rating ID has changed.
2 = Parallel connection rating ID has
changed.
3 = PU types not the same in all power
units.
4 = Parallel connection rating ID is active
in a single power unit setup.
5 = It is not possible to implement the
selected rating with the current PUs.
6 = PU rating ID is 0.
7 = Reading PU rating ID or PU type
failed on PU connection.
8 = PU not supported (illegal rating ID).
With parallel connection faults (BCU
control unit), the format of the auxiliary
code is 0X0Y. “Y” indicates the auxiliary
code category, “X” indicates the first
faulty PU channel in hexadecimal (1…C).
(With a ZCU control unit, “X” can be 1 or
2 but this is irrelevant to the fault.)
5094
Measurement circuit
temperature
Problem with internal
temperature measurement of
the drive.
See
5681
PU communication
The way the control unit is
powered does not correspond
to parameter setting.
Check setting of
.
Communication errors
detected between the drive
control unit and the power unit.
Check the connection between the
control unit and the power unit.
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected modules,
“Y YY” specifies the affected BCU control
unit channel (
0:
broadcast). “ZZ”
specifies the error source (
1:
Transmitter
side [link error],
2:
Transmitter side [no
communication],
3:
Receiver side [link
error],
4:
Receiver side [no
communication],
5:
Transmitter FIFO
error [see “XXX”],
6:
Module [xINT board]
not found,
7:
BAMU board not found).
“XXX” specifies the transmitter FIFO
error code (
1:
Internal error [invalid call
parameter],
2:
Internal error
[configuration not supported],
3:
Transmission buffer full).
5682
Power unit lost
Connection between the drive
control unit and the power unit
is lost.
Check the connection between the
control unit and the power unit.
5690
PU communication
internal
Internal communication error.
Contact your local ABB representative.
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact your local ABB representative,
quoting the auxiliary code.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...