12 ACS880-01/04 +C132 marine type-approved drives
Electrical installation
IT (ungrounded) networks
The ground-to-phase varistor of the drive is not suitable for use on an IT
(ungrounded) system. Disconnect it (also from marine type-approved drives with
E201) before you connect the drive to the supply network. For disconnecting
instructions, see
EMC filter and ground-to-phase varistor disconnecting instructions
for ACS880 frames R1 to R11
(3AUA0000125152 [English]) or contact ABB.
WARNING!
Do not install the drive with the ground-to-phase varistor
connected on an IT system (an ungrounded power system or a high-
resistance-grounded [over 30 ohms] power system). The varistor circuit and the drive
can be damaged.
Connecting the power cables
Connection diagram
See the hardware manual.
Connection procedure – ACS880-01
1. Install the input power cable (and brake resistor cable, if present) as shown in the
hardware manual.
2. Install the common mode filter ring to the cable entry box. If the cable entry box is
not used (P940), hang the ring on the cabinet structure.
For instructions, see the applicable installation guide:
•
Common mode filter kit for ACS880-01 drives (frame R6, E208)
installation guide
(3AXD50000015178
[English])
•
Common mode filter kit for frames R7 and R8, E208 installation guide
(3AXD50000015179 [English])
•
Common mode filter kit for ACS880-01 drives (frame R8, E208)
installation guide
(3AXD50000015180
[English])
•
Common mode filter kit for ACS880-01 drives (frame R9, E208)
installation guide
(3AXD50000015201 [English]).
3. Route the motor cable through the ring as shown in the installation guide.
Connection procedure – ACS880-04
See the hardware manual.