128 Parameters
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000 mA or
V
-22.000 … 22.000
mA or V
Minimum value of AI2.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
.
20.000 mA or
10.000 V
-22.000 … 22.000
mA or V
Maximum value of AI2.
1000 = 1 mA
or V
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
(Changing the polarity settings of
can
effectively invert the analog input.)
0.000
-32768.000 …
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
.
.
100.000
-32768.000 …
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
13
Configuration of standard analog outputs.
Displays the value of AO1 in mA.
This parameter is read-only.
-
0.000 … 22.000 mA Value of AO1.
1000 = 1 mA
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
Zero
None.
0
Motor speed used
(page
).
1
Output frequency
).
3
Motor current
(page
4
No.
Name/Value
Description
Def
/
FbEq16
AI
in
(
AI
scaled
(
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...