Program features 79
The intermediate DC circuit is charged over an internal resistor which is bypassed
when the capacitors are considered charged and the voltage has stabilized.
Settings
Parameter group
(page
Brake chopper
The built-in brake chopper of the drive can be used to handle the energy generated
by a decelerating motor.
When the brake chopper is enabled and a resistor connected, the chopper will start
conducting when the DC link voltage of the drive reaches
U
DC_BR
- 30 V. The
maximum braking power is achieved at
U
DC_BR
+ 30 V.
U
DC_BR
= 1.35 × 1.25 ×
.
Settings
Parameter group
(page
).
Undervoltage control level (0.8 ×
U
DC
; 400 V min.)
Undervoltage fault level (
U
DC,
low - 50 V; 350 V min.)
Overvoltage control level (1.25 ×
U
DC
; 810 V max.)
Overvoltage fault level (
U
DC,
high + 70 V; 880 V max.)*
U
DC
= 1.35 ×
U
DC
, high = 1.25 ×
U
DC
U
DC
, low = 0.8 ×
U
DC
*Drives with 230 V supply voltage (ACS850-04-xxxx-2): The overvoltage fault
level is set to 500 V.