Control through the embedded fieldbus interface 327
References for the ABB Drives profiles
The ABB Drives profiles support the use of two fieldbus references, REF1 and REF2.
The references are 16-bit words each containing a sign bit and a 15-bit integer. A
negative reference is formed by calculating the two’s complement from the
corresponding positive reference.
The fieldbus references are scaled before they are written into signals
for the use in the drive. Parameters
define the scaling and possible use of the
fieldbus reference REF1 and REF2 as follows:
, the fieldbus reference can be used as a speed
reference and it is scaled as follows:
, the fieldbus reference can be used as a torque
reference and it is scaled as follows:
, the fieldbus reference REF1 or REF2 is the drive
reference without scaling.
1)
Unit depends on the use of the reference in the drive. Rpm for speed reference and % for torque.
Fieldbus reference REF1 or REF2
[integer]
Corresponding speed reference
in the drive [rpm]
20 000
0
0
-20 000
-(value of parameter
)
Fieldbus reference REF1 or REF2
[integer]
Corresponding torque reference
in the drive [%]
10 000
100% of motor nominal torque
0
0
-10 000
-(100% of motor nominal torque)
Fieldbus reference REF1 or REF2
[integer]
Corresponding reference
in the drive [rpm or %]
1)
32 767
32 767
0
0
-32 768
-32 768
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...