Planning the electrical installation
43
Selecting the power cables
General rules
Dimension the supply (input power) and motor cables
according to local
regulations
.
• The cable must be able to carry the drive load current. See the chapter
for the rated currents.
• The cable must be rated for at least 70
°
C (US: 75 °C [167 °F]) maximum
permissible temperature of conductor in continuous use.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 VAC cable is accepted for up to 500 VAC.
• Refer to the chapter
Symmetrical shielded motor cable must be used (see the figure below) to meet the
EMC requirements of the CE and C-tick marks.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made of the same metal as the phase
conductors:
Compared to a four-conductor system, the use of symmetrical shielded cable
reduces electromagnetic emission of the whole drive system as well as motor
bearing currents and wear.
The motor cable and its PE pigtail (twisted shield) should be kept as short as
possible in order to reduce electromagnetic emission, as well as stray currents
outside the cable and capacitive current.
Cross-sectional area of one phase conductor
(S)
Minimum cross-sectional area of protective
conductor (S
p
)
S < 16 mm
2
S
16 mm
2
< S < 35 mm
2
16 mm
2
35 mm
2
< S
S/2
Summary of Contents for ACS850 series
Page 1: ...ACS850 Hardware Manual ACS850 04 Drive Modules 1 1 to 45 kW...
Page 2: ......
Page 4: ......
Page 14: ...Table of contents 14...
Page 20: ...About this manual 20...
Page 32: ...Planning the cabinet assembly 32...
Page 38: ...Mechanical installation 38...
Page 48: ...Planning the electrical installation 48...
Page 50: ...Electrical installation 50 1 2 3 4 5...
Page 68: ...Electrical installation 68...
Page 76: ...Maintenance 76...
Page 102: ...du dt and common mode filtering 102...
Page 108: ...Dimension drawings 108 Frame size A...
Page 109: ...Dimension drawings 109 Frame size B...
Page 110: ...Dimension drawings 110 Frame size C...
Page 111: ...Dimension drawings 111 Frame size D...
Page 113: ...Dimension drawings 113 EMC filters type JFI x1 JFI A1...
Page 114: ...Dimension drawings 114 JFI B1...
Page 115: ...Dimension drawings 115 EMC filters type JFI 0x...
Page 117: ...Dimension drawings 117 Braking resistors type JBR xx...