Parameters 69
02.24
FBA main sw
Status Word for fieldbus communication. See also chapter
, page
-
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
0
Ready
1
Drive is ready to receive Start command.
0
Drive is not ready.
1
Enabled
1
External Run enable signal is received.
0
No external Run enable signal is received.
2
Running
1
Drive is modulating.
0
Drive is not modulating.
3
Ref running
1
Normal operation is enabled. Drive is running and following given
reference.
0
Normal operation is disabled. Drive is not following given reference
(for example, it is modulating during magnetization).
4
Em off
(OFF2)
1
Emergency OFF2 is active.
0
Emergency OFF2 is inactive.
5
Em stop
(OFF3)
1
Emergency stop OFF3 (ramp stop) is active.
0
Emergency stop OFF3 is inactive.
6
Ack startinh
1
Start inhibit is active.
0
Start inhibit is inactive.
7
Alarm
1
An alarm is active. See chapter
.
0
No alarm is active.
8
At setpoint
1
Drive is at setpoint. Actual value equals reference value (i.e. the
difference between the actual speed and speed reference is within
the speed window defined by parameter
0
Drive has not reached setpoint.
(continued)