Parameters 197
Auto falling
One of the above modes is selected automatically depending
on the TTL pulse frequency as follows:
5
93.11
Enc2 pulse nr
Defines the pulse number per revolution for encoder 2.
0 … 65535
Number of pulses for encoder 2.
1 = 1
93.12
Enc2 type
Selects the type of the encoder 2.
Quadrature
Quadrature encoder (has two TTL channels, channels A
and B)
0
Single track
Single track encoder (has one TTL channel, channel A)
1
93.13
Enc2 sp CalcMode
Selects the speed calculation mode for encoder 2.
A&B all
See parameter
0
A all
See parameter
1
A rising
See parameter
2
A falling
See parameter
3
Auto rising
See parameter
4
Auto falling
See parameter
5
94
94 Ext IO conf
I/O extension configuration.
94.01
Ext IO1 sel
Activates an I/O extension installed into Slot 1.
None
No extension installed into Slot 1.
0
FIO-01
FIO-01 extension installed into Slot 1.
1
FIO-11
FIO-11 extension installed into Slot 1.
2
FIO-21
FIO-21 extension installed into Slot 1.
3
94.02
Ext IO2 sel
Activates an I/O extension installed into Slot 2.
None
No 2nd extension installed into Slot 2.
0
FIO-01
FIO-01 extension installed into Slot 2.
1
FIO-11
FIO-11 extension installed into Slot 2.
2
FIO-21
FIO-21 extension installed into Slot 2.
3
95
95 Hw configuration
Diverse hardware-related settings.
95.01
Ctrl boardSupply
Selects how the drive control unit is powered.
Internal 24V
The drive control unit is powered from the drive power unit it
is mounted on. This is the default setting.
0
External 24V
The drive control unit is powered from an external power
supply.
1
No.
Name/Value
Description
FbEq
Pulse frequency of the channel(s) Mode used
< 2442 Hz
2442…4884 Hz
> 4884 Hz