Parameters 137
25.02
Crit speed1 lo
Defines the low limit for critical speed range 1.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 1.
1 = 1 rpm
25.03
Crit speed1 hi
Defines the high limit for critical speed range 1.
Note:
This value must be greater than or equal to the value of
.
-30000 … 30000
rpm
High limit for critical speed 1.
1 = 1 rpm
25.04
Crit speed2 lo
Defines the low limit for critical speed range 2.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 2.
1 = 1 rpm
25.05
Crit speed2 hi
Defines the high limit for critical speed range 2.
Note:
This value must be greater than or equal to the value of
.
-30000 … 30000
rpm
High limit for critical speed 2.
1 = 1 rpm
25.06
Crit speed3 lo
Defines the low limit for critical speed range 3.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 3.
1 = 1 rpm
25.07
Crit speed3 hi
Defines the high limit for critical speed range 3.
Note:
This value must be greater than or equal to the value of
.
-30000 … 30000
rpm
High limit for critical speed 3.
1 = 1 rpm
26
26 Constant speeds
Constant speed selection and values. An active constant
speed overrides the drive speed reference. See section
.
26.01
Const speed func
Determines how constant speeds are selected, and whether
the rotation direction signal is considered or not when
applying a constant speed.
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Const speed
mode
1 = Packed: 7 constant speeds are selectable using the three sources
defined by parameters
,
and
0 = Separate: Constant speeds 1, 2 and 3 are separately activated by
the sources defined by parameters
and
respectively.
In case of conflict, the constant speed with the smaller number takes
priority.
1
Dir ena
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters
) is
multiplied by the direction signal (forward: +1, reverse: -1). For example,
if the direction signal is reverse and the active constant speed is
negative, the drive will run in the forward direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
).
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 2: ......
Page 4: ......
Page 24: ...24 Start up...
Page 28: ...28 Control locations and operating modes...
Page 252: ...252 Fieldbus control...