Planning the electrical installation
59
Additional US requirements
Use type MC continuous corrugated aluminum armor cable with symmetrical
grounds or shielded power cable for the motor cables if metallic conduit is not used.
For the North American market, 600 V AC cable is accepted for up to 500 V AC. For
drives rated over 100 amperes, the power cables must be rated for 75
°
C (167
°
F).
Conduit
Couple separate parts of a conduit together: bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Bond the conduits also to
the drive enclosure and motor frame. Use separate conduits for input power, motor,
brake resistor, and control wiring. When conduit is employed, type MC continuous
corrugated aluminium armor cable or shielded cable is not required. A dedicated
ground cable is always required.
Note
: Do not run motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminum
armor cable with symmetrical grounds is available from the following suppliers (trade
names in parentheses):
• Anixter Wire & Cable (Philsheath)
• BICC General Corp (Philsheath)
• Rockbestos Co. (Gardex)
• Oaknite (CLX).
Shielded power cables are available from Belden, LAPPKABEL (ÖLFLEX) and
Pirelli.
Selecting the control cables
Shielding
All control cables must be shielded.
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Employ one individually shielded
pair for each signal. Do not use common return for different analog signals.
Insulation jacket
Copper wire screen
Helix of copper tape
or copper wire
Cable core
Inner insulation
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...