Planning the electrical installation 55
Compared to the four conductor system, the use of symmetrical shielded cable reduces
electromagnetic emission of the whole converter system as well as generator bearing
currents and wear.
Note:
The cabinet configuration of the converter may require multiple supply and/or
generator cabling. Refer to the connection diagrams in chapter
The generator cable and its PE pigtail (twisted screen) should be kept as short as possible
in order to reduce electromagnetic emission as well as capacitive current.
Typical power cable sizes
IEC
The maximum number of cables to be connected are shown below.
Rotor-side converter cables
Grid-side converter cables (or cables to the power cabinet (C109))
UL
The maximum number of cables to be connected are shown below. The cable ratings are
based on UL508A and National Electric Code 2008 (US).
Rotor-side converter cables
Type name
Rotor-
side
converter
current
rating [A]
240mm
2
185mm
2
120mm
2
3×240mm
2
+ 120mm
2
3×185mm
2
+
95mm
2
3×120mm
2
+
70mm
2
nr of cables / phase
nr of cables
ACS800-67LC-1075/0575-7
898
2
3
4
3
3
4
ACS800-67LC-1375/0575-7
1143
3
4
5
3
4
5
ACS800-67LC-1375/1125-7
1143
3
4
5
3
4
5
ACS800-67LC-1595/0865-7
1334
4
4
6
4
5
6
ACS800-67LC-2035/1125-7
1697
5
5
7
5
6
8
Type name
Grid-side
converter
current
rating [A]
240mm
2
185mm
2
120mm
2
3×240mm
2
+
120mm
2
3×185mm
2
+
95mm
2
3×120mm
2
+
70mm
2
nr of cables / phase
nr of cables
ACS800-67LC-1075/0575-7
480
1
2
2
2
2
2
ACS800-67LC-1375/0575-7
480
1
2
2
2
2
2
ACS800-67LC-1375/1125-7
941
3
3
4
3
3
4
ACS800-67LC-1595/0865-7
720
2
2
3
2
3
3
ACS800-67LC-2035/1125-7
941
3
3
4
3
3
4
Type name
Rotor-side converter
current rating [A]
500 kcmil (253 mm
2
) 350 kcmil (177 mm
2
)
nr of cables / phase
ACS800-67LC-1075/0575-7
898
4
5
ACS800-67LC-1375/0575-7
1143
6
8
ACS800-67LC-1375/1125-7
1143
6
8
ACS800-67LC-1595/0865-7
1334
6
9
ACS800-67LC-2035/1125-7
1697
9
11
Summary of Contents for ACS800-67LC
Page 1: ... ABB WIND TURBINE CONVERTERS ACS800 67LC wind turbine converters Hardware manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 52: ...52 Mechanical installation ...
Page 79: ...Electrical installation 79 3 3 Rotor side cable connection terminals U2 V2 W2 ...
Page 92: ...92 Maintenance 4 6 5 5 ...
Page 103: ...Maintenance 103 Bussmann fuses Mersen fuses ...
Page 109: ...Maintenance 109 5 6 7 ...
Page 131: ...Technical data 131 Declaration of incorporation ...
Page 136: ...136 Dimension drawings ACS800 67LC 1075 0575 7 and 1375 0575 7 ...
Page 137: ...Dimension drawings 137 With 400 mm wide incoming cubicle option C111 ...
Page 138: ...138 Dimension drawings ACS800 67LC 1375 1125 7 ...
Page 139: ...Dimension drawings 139 With 400 mm wide incoming cubicle option C111 ...
Page 140: ...140 Dimension drawings ACS800 67LC 1595 0865 7 and 2035 1125 7 ...
Page 141: ...Dimension drawings 141 With 400 mm wide incoming cubicle option C111 ...
Page 143: ...Dimension drawings 143 Options 2H370 and C111 Option 1H371 ...
Page 144: ...144 Dimension drawings Options 1H371 and C111 Options 2H371 and C111 ...
Page 145: ...Dimension drawings 145 Option H378 Options H378 and C111 ...
Page 147: ...Dimension drawings 147 Option 2H372 ...
Page 148: ...148 Dimension drawings Option 3H372 ...
Page 149: ...Dimension drawings 149 Option 1H373 ...
Page 150: ...150 Dimension drawings Option 2H373 ...
Page 151: ...Dimension drawings 151 Option 3H373 ...