38 System description
Stator contactor (par. 16.20 GRID CONNECT MODE set to
MCB1+MCB3/C)
The configuration below is used when MCB1 and MCB3 are connected in series.
The breaking device type for the grid connection is defined by parameter 20.27 CONT
OPEN CUR.
•
0 A = main circuit breaker or medium voltage circuit breaker MCB3 is used for
disconnecting stator from grid
•
> 0 A = contactor MCB3 is used for disconnecting stator from grid.
When parameter value [> 0 A] is selected, the converter can be disconnected from the grid
in two ways depending on a parameter setting:
•
If measured current 06.29 STATOR IS NO FILT is below the parameter value, the
converter uses the stator contactor only.
•
If measured current 06.29 STATOR IS NO FILT is above the parameter value, the
converter first opens the breaker and, after a short time, the stator contactor.
The parameter value is compared to unfiltered stator rms value. Since the unfiltered value
always contains a certain amount of noise, it is recommended to set the parameter to a
value of contactor nominal c15%. See the delivery specific circuit diagrams.
Settings
Parameter 20.27 CONT OPEN CUR.
In case of one contactor, the value for parameter 20.27 CONT OPEN CUR is the nominal
current of the contactor.
ISU
INU
G
MCB1
MCB3
MCB2
Turbine
transformer
MCB1
stator breaker
MCB2
converter contactor
MCB3
stator contactor
Summary of Contents for ACS800-67
Page 4: ......
Page 76: ...76 Start up with medium voltage stator ...
Page 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Page 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Page 118: ...118 Tracing the source of warnings limits and faults ...
Page 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...