Practical examples 109
Italian grid code
Parameter
Setting
Control program AJXC2330 (or newer) parameters:
4.04 DEVICE ID
INU 800 1160_7NC
20.23 USER KVAR LIMIT
100%
30.05 AC OVERVOLT TRIP
828
30.06 AC UNDERVOLT TRIP (2) (V)
69
30.07 AC OVERFREQ TRIP
53 Hz
30.08 AC UNDERFREQ TRIP
47 Hz
30.15 DLYED AC OV TRIP (V)
759
30.16 AC OV TRIP DLY (s)
1.5
31.01 CROWBAR HW TYPE
ACTIVE CB
32.01 GRID SUPPORT MODE
MAX. Up-p
32.02 RT MONITOR SIGNAL
MIN. Up-p
32.03 RT U/Un LEVEL1 (1)
85%
32.04 RT U/Un LEVEL2 (4)
10%
32.05 RT U/Un LEVEL 3 (5)
75%
32.06 RT U/Un DELTA t1 (6) (ms)
800
32.07 RT U/Un DELTA t2 (3) (ms)
500
32.08 RT U/Un DELTA t3 (8) (ms)
2000
32.09 RT U/Un DELTA t4 (ms)
0 ms
32.10 RT U/Un LEVELHYST (7)
10%
32.11 GS U/Un LEVEL 1
90%
32.12 GS U/Un LEVEL 2
80%
32.13 GS U/Un LEVEL 3
25%
32.14 GS U/Un LEVEL 4
15%
32.15 GS U/Un LEVEL 5
110%
32.16 GS U/Un LEVEL 6
120%
32.17 GS IQREF LEVEL 1
0%
32.18 GS IQREF LEVEL 2
112%
32.19 GS IQREF LEVEL 3
112%
32.20 GS IQREF LEVEL 4
112%
32.21 GS IQREF LEVEL 5
-20%
32.22 GS IQREF LEVEL 6
-40%
32.23 GS AFTER DIP
0%
32.24 GS TIME AFTER DIP
0 ms
32.25 KVAR RISE TIME
50 ms
32.26 TORQUE RISE TIME
50 ms
32.27 Imax/In (LVRT)
124%
32.28 TMIN/TN (LVRT)
1%
32.29 Ip max/In (LVRT)
118%
32.30 IR MAX PEAK LEVEL
1777.66 A
32.31 IR MAXSLOPE SCALE
507.903 A
32.32 U- / U+ START DIS
80%
32.33 U(RMS) START DIS
10%
32.34 RT U/Un DELTA t5 (10) (s)
3
Summary of Contents for ACS800-67
Page 4: ......
Page 76: ...76 Start up with medium voltage stator ...
Page 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Page 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Page 118: ...118 Tracing the source of warnings limits and faults ...
Page 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...