Operation
77
Fixed parameters with the ACS800-11, ACS800-U11 and ACS800-17
When the IGBT Supply Control Program is loaded into the ACS800-11, ACS800-U11
or ACS800-17, the following parameters receive the default values given in the table
below.
31.02
TRIAL TIME
Defines the time for the automatic fault reset function. See parameter
31.01.
R
30 s
1.0 … 180.0 s
Allowed resetting time
100 …
18000
31.03
DELAY TIME
Defines the time that the drive will wait after a fault before attempting
an automatic reset. See parameter 31.01.
R
0 s
0.0 … 3.0 s
Resetting delay
0 … 300
31.04
OVERCURRENT
Activates/deactivates the automatic reset for the line converter
overcurrent fault.
B
NO
NO
Inactive
0
YES
Active
65535
31.05
OVERVOLTAGE
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault.
B
NO
NO
Inactive
0
YES
Active
65535
31.06
UNDERVOLTAGE
Activates/deactivates the automatic reset for the intermediate link
undervoltage fault.
B
NO
NO
Inactive
0
YES
Active
65535
Parameter
Default value
If changed,
11.01
DC REF SELECT
FIELDBUS
the default values will be
restored on the next power-
up
11.02
Q REF SELECT
PARAM 24.02
98.01
COMMAND SEL
MCW.
Note:
If par. 16.15 I/O
START MODE is set to DI2 LEVEL,
the default value is changed to I/O
on the next RMIO board power-up.
98.02
COMM. MODULE
INVERTER
201.09
PANEL DRIVE ID
2
202.01
LOCAL LOCK
TRUE
30.02
EARTH FAULT
FAULT.
Note conserning the ACS800-11:
The line converter is not equipped
with earth fault supervision.
the default values will not
be restored on the next
power-up. Do not change
them. If the default values
are changed, the drive will
not function.
70.01
CH0 NODE ADDR
120
70.19
CH0 HW CONNECTION RING
70.20
CH3 HW CONNECTION RING
71.01
CH0 DRIVEBUS MODE NO
No.
Name/Value
Description
T./FbEq Def.
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......