ABB ACS800-07 Manual Download Page 1

ABB industrial drives

Description
Cabinet Options for ACS800-07/U7/17/37

Summary of Contents for ACS800-07

Page 1: ...ABB industrial drives Description Cabinet Options for ACS800 07 U7 17 37...

Page 2: ...ate 32 E202 EMC filter for drives of category 2 in TN systems 20 H359 Common motor terminal cubicle 32 E210 EMC filter for drives of category 3 in TN or IT systems 20 L505 2L505 Thermistor relays 1 or...

Page 3: ...Cabinet Options for ACS800 07 U7 17 37 Description 3AUA0000053130 Rev A EN EFFECTIVE 27 3 2009 2009 ABB Oy All Rights Reserved...

Page 4: ......

Page 5: ...nual 9 Related documents 9 Contents 10 Standard features Degree of protection B General 13 Definitions 14 IP22 B053 14 IP42 B054 14 IP54 B055 14 IP54R B059 15 Calculating the required static pressure...

Page 6: ...ACS800 07 24 gG line fuses F251 24 aR line fuses F260 25 Load switch F253 25 Load switch for 12 pulse units A004 F253 25 Air circuit breaker F255 26 Grounding switch F259 27 Availability table 27 Heat...

Page 7: ...ion 33 Example connection diagram 34 Pt100 relays 3L506 5L506 8L506 34 What the option contains 34 Description 35 Example connection diagram 35 Setting the alarm and trip levels of the Pt100 relay 35...

Page 8: ...Table of contents 8...

Page 9: ...configuring tool for internal use Safety instructions Target audience The manual is intended for ABB sales and sales support personnel and drive application engineers Purpose of the manual The purpos...

Page 10: ...Introduction to the manual 10 Contents The manual lists the standard cabinet features of different drive types and describes the available options in alphabetic order...

Page 11: ...L type 1 main switch fuse with aR fuses line contactor 230 V AC auxiliary control voltage control panel CDP312R standard control program EMC filtering Category 3 TN or IT systems E210 du dt filtering...

Page 12: ...Standard features 12 More information ACS800 Ordering Information 3AFE64556568...

Page 13: ...s open the degree of protection of the standard cabinet and all cabinet options is IP20 The live parts inside the cabinet are protected against contact with clear plastic shrouds or metallic gratings...

Page 14: ...fabric air filter mats between the inner metallic grating and the outer plastic grating ACS800 07 frame R6 The option may contain an additional fan ACS800 07 frames R7 and R8 The option contains an ad...

Page 15: ...sure that no dirty or moist air is able to flow backward to the drive in any case even during off time or while servicing the drive or the ventilation system Calculating the required static pressure d...

Page 16: ...rking option G338 G342 page 30 according to the requirements of the classification society Related options halogen free materials and wiring G330 More information Hardware manual UL listed C129 The op...

Page 17: ...following accessories and features US CSA type main switch fuse bottom entry and exit of cables US cable conduit entry plain plate without ready made holes 115 VAC control voltage when needed all comp...

Page 18: ...engineered option Not available for ACS800 17 More information Hardware manual and NBRA 6xx Braking Choppers Installation and Start up Guide 3AFY58920541 English Brake resistors D151 The option contai...

Page 19: ...nly by a professional when used in the first environment Drive of category C3 drive of rated voltage less than 1000 V and intended for use in the second environment and not intended for use in the fir...

Page 20: ...able for ACS800 17 37 frame R6 du dt filter E205 The du dt filter protects the motor insulating system by reducing the voltage rise speed at the motor terminals The filter also protects the motor bear...

Page 21: ...rings mounted around the drive DC busbars The filter protects the motor bearings by reducing the bearing currents ACS800 07 and ACS800 U7 Not available for frames R5 and R6 except 0135 3 0165 3 0205 3...

Page 22: ...ACS800 U7 frames R6 to R8 The cabinet is equipped with an US switch fuse type of main switch which contains Class T or L fuses ACS800 07 frames n R8i Standard features The supply modules are equipped...

Page 23: ...rapid semiconductor fuses Class aR and with a line contactor optional in frame R6 standard in frames R7i and R8i More information Hardware manual ACS800 17 and ACS800 37 frames n R8i Standard features...

Page 24: ...27 English Frames n R8i ACS800 07 This option provides a line contactor inside each supply module Other required options Emergency stop function Q951 or Q952 see page 39 Not available for ACS800 17 an...

Page 25: ...witches Option for ACS800 07 frames n R8i Other required options F260 Related options F259 Not available for ACS800 07 U7 frames R5 to R8 ACS800 17 and ACS800 37 Load switch for 12 pulse units A004 F2...

Page 26: ...against short circuits With this option the internal load switches are removed from the supply modules Option for ACS800 07 frames n R8i Standard for ACS800 17 and ACS800 37 Other required options F2...

Page 27: ...types 1 The customer must take care of the protection according to the instructions given in ACS800 07 Hardware Manual 3AFE64731165 English 2 With load switch option the internal main switch is remov...

Page 28: ...al power supply Description The heater prevents humidity condensation inside the cabinet when the drive is not powered The power output of the semiconductor type heating elements depends on the enviro...

Page 29: ...ystem Board DSSB Output for motor heater G313 The option contains a padlockable load switch a miniature circuit breaker for short circuit protection and a terminal block for external supply and heatin...

Page 30: ...ves thus reducing toxic fire gases Additional wire markings G338 G342 As standard only drive input and output terminals plug in connectors fibre optic connectors and ribbon cables are marked The wire...

Page 31: ...chable screw terminals Main circuit conductors and also short and obvious connections are marked G342 Equipment identifications and terminal block pin numbers and remote addresses are marked by rings...

Page 32: ...and EMC sleeves and cushions US UK gland conduit plate H358 The option provides US UK conduit plates plain 3 m steel plates without any ready made holes US UK conduit plates are provided as standard w...

Page 33: ...minal blocks of all cabinet options except M600 to M606 are of the same type as terminal block X2 Note The optional modules inserted in the slots of the I O board are not wired to the additional termi...

Page 34: ...otor overtemperature or appropriate digital input of the drive for tripping the drive and generating a fault message in case of motor overtemperature or customer control circuit More information See t...

Page 35: ...liary relays of the normally open contacts of the Pt100 relays for example to main breaker control circuit of the drive for opening the breaker in case of motor overtemperature or appropriate digital...

Page 36: ...150 C when both alarm and trip are used ATEX certified thermal protection with PTC L513 The option contains an ATEX certified thermistor relay Description In combination with safety option Q950 the op...

Page 37: ...block for output X6 The maximum wire cross section accepted by the terminal block is 6 mm2 The fan voltage is the same as the drive nominal voltage Description The drive controls the auxiliary motor...

Page 38: ...for auxiliary motor fan M 38 Trip limit setting ranges Option code Manual motor starter trip limit setting range M600 1 1 6 A M601 1 6 2 5 A M602 2 5 4 A M603 4 6 3 A M604 6 3 10 A M605 10 16 A M605...

Page 39: ...following safety options Option code Function Notes Q950 Prevention of Unexpected Start Q951 Category 0 emergency stop In frames R5 to R8 also option F250 is required In frames n R8i also options F25...

Page 40: ...Safety features Q 40...

Page 41: ......

Page 42: ...bb com ABB Inc Automation Technologies Drives Motors 16250 West Glendale Drive New Berlin WI 53151 USA Telephone 262 785 3200 800 HELP 365 Fax 262 780 5135 Internet www abb com ABB Beijing Drive Syste...

Reviews: