Technical data
87
The calculated short-circuit current 9.7 kA is higher than the minimum short-circuit current of the drive
gG fuse type OFAF3H500 (8280 A). -> The 500 V gG fuse (ABB Control OFAF3H500) can be used.
Fuse tables
gG fuses
ACS800-04
size
Input
current
Min. short-
circuit
current
1)
Fuse
A
A
A
A
2
s
V
Manufacturer
Type
IEC size
Three-phase supply voltage 208 V,
220 V,
230 V
or 240 V
-0080-2
201
3820
250
550 000
500
ABB Control
OFAF1H250
1
-0100-2
239
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0120-2
285
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0140-2
391
8280
500
2 900 000
500
ABB Control
OFAF3H500
3
-0170-2
428
8280
500
2 900 000
500
ABB Control
OFAF3H500
3
-0210-2
506
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0230-2
599
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0260-2
677
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
-0300-2
707
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
Three-phase supply voltage 380 V,
400 V
or 415 V
-0140-3
196
3820
250
550 000
500
ABB Control
OFAF1H250
1
-0170-3
237
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0210-3
286
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0260-3
438
8280
500
2 900 000
500
ABB Control
OFAF3H500
3
-0320-3
501
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0400-3
581
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0440-3
674
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
-0490-3
705
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
m
·
0.112
ohm
km
= 19.04 mohm
R
c
= 170
m
·
0.0273
ohm
km
= 4.641 mohm
X
c
= 170
=
410 V
2
·
(19.04 mohm)
2
+ (4.438 mohm + 4.641 mohm)
2
I
k2-ph
= 9.7 kA
Summary of Contents for ACS800-04
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 54: ...Planning the electrical installation 54 ...
Page 72: ...Motor control and I O board RMIO 72 ...
Page 116: ...Resistor braking 116 ...
Page 117: ......