Technical data
97
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/
EEC, as amended by 93/68/EEC).
Definitions
EMC stands for
E
lectro
m
agnetic
C
ompatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used
within the European Union. The EMC product standard [EN 61800-3 + Amendment A11 (2000)] covers
requirements stated for drives.
First environment
includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment
includes establishments connected to a network not supplying domestic premises.
Restricted distribution:
mode of sales distribution in which the manufacturer restricts the supply of
equipment to suppliers, customers or users who separately or jointly have technical competence in the
EMC requirements of the application of drives.
Unrestricted distribution:
mode of sales distribution in which the supply of equipment is not dependent
on the EMC competence of the customer or user for the application of drives.
Compliance with the EMC Directive
First environment
The requirements of the EMC Directive can be met as follows for restricted distribution:
1. The drive is equipped with EMC filter E202.
2. The motor and control cables are selected as specified in the
Hardware Manual
.
3. The drive is installed according to the instructions given in the
Hardware Manual
.
4. Maximum cable length is 100 metres.
WARNING!
The drive may cause radio interference if used in a residential or domestic environment.
The user is required to take measures to prevent interference, in addition to the requirements for CE
compliance listed above, if necessary.
Note:
It is not allowed to install a drive equipped with EMC filter E202 on IT (unearthed) systems. The
supply network becomes connected to earth potential through the EMC filter capacitors which may
cause danger or damage the unit.
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......