Electrical installation 71
For further information on locating the temperature sensor cables, auxiliary power supply
cables and the optional heating cable, see
Cable entries for external connections
Power cable terminals are located in the terminal compartment behind the control
compartment. They can be accessed after removing the metal cover (tripping loop
terminals -XS1 on the cover must be opened first).
The drive is prepared for top or bottom cable entry with one or a combination of the following
cable entries:
•
Metal plate hole cable entry for power cables, ground cables
•
Cable entry with EMC plates, EMC cushions and sealing grommets for auxiliary and
control cables
For detailed information e.g. location and dimensions, see
ACS580MV Base frame & TEU
layout design.
Power cable entry via holes in cable entry plate
Power cable entry can be from bottom or top.
Galvanized plate for cable entry.
for more information.
Control and auxiliary cable entry with EMC plates
Cable entry can be from bottom or top.
1
2
3
1
Power cable entry plate (in TEU)
2
Auxiliary and control cable entry (in COU)
3
Sealing compound
Summary of Contents for ACS580MV
Page 1: ...ABB industrial drives Hardware manual ACS580MV drives 200 kW to 6300 kW 6 kV to 11 kV...
Page 4: ......
Page 10: ...10...
Page 50: ...50 Control system and interfaces...
Page 52: ...52 Guidelines for planning the electrical installation...
Page 77: ...Electrical installation 77 Power cable entry from top 1 screen extensions to ground 1...
Page 90: ...90 Installation checklist...
Page 142: ...142 Maintenance...
Page 144: ......
Page 146: ...Contact us 2UBB004520 Rev E EN 2019 06 27 www abb com drives www abb com drivespartners...