Guidelines for planning the electrical installation 51
Requirements table
The following table shows how to select the motor insulation system and when ABB
requires optional drive du/dt and common mode filters and insulated N-end (non-drive
end) motor bearings. If the installation does not fulfill these requirements or improper
installation can shorten motor life or damage the motor bearings and voids the warranty.
The abbreviations used in the table are defined below.
Motor
type
Nominal AC supply
voltage
Requirement for
Motor
insulation
system
ABB d
u
/d
t
and common mode filters, insulated N-end
motor bearings
100 kW <
P
N
<
350 kW
or
IEC 315 < frame size <
IEC 400
P
N
>
350 kW
or
frame size > IEC 400
ABB motors
Random
-wound
M2_,
M3_ and
M4_
U
N
< 500 V
Standard
+ N
+ N + CMF
Form-
wound
HX_ and
AM_
380 V <
U
N
< 690 V
Standard
+ N + CMF
P
N
<
500 kW:
+N + CMF
P
N
>
500 kW
+N + d
u
/d
t
+ CMF
Old*
form-
wound
HX_ and
modular
380 V <
U
N
< 690 V
Check with
the motor
manufacturer.
+ N + d
u
/d
t
with voltages over 500 V + CMF
Random
-wound
HX_ and
AM_ **
0 V <
U
N
< 500 V
Enamelled
wire with fiber
glass taping
+ N + CMF
HDP
Consult the motor manufacturer.
*
manufactured before 1.1.1998
**
For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
Non-ABB motors
Random
-wound
and
form-
wound
U
N
< 420 V
Standard:
Û
LL
= 1300 V
+ N or CMF
+ N + CMF
420 V <
U
N
< 500 V
Standard:
Û
LL
= 1300 V
+ d
u
/d
t
+ (N or CMF)
+ N + d
u
/d
t
+ CMF
or
Reinforced:
Û
LL
= 1600 V,
0.2
microsecond
rise time
+ N or CMF
+ N + CMF
Abbr.
Definition
U
N
Nominal AC line voltage
Û
LL
Peak line-to-line voltage at motor terminals which the motor insulation must withstand
P
N
Motor nominal power
du/dt
du/dt filter at the output of the drive (E205)
Summary of Contents for ACS580-07-0495A-4
Page 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Page 4: ......
Page 8: ...4 Update notice ...
Page 16: ...12 ...
Page 24: ...20 Safety instructions ...
Page 42: ...38 Operation principle and hardware description ...
Page 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 82: ...78 Electrical installation ...
Page 102: ...98 Fault tracing ...
Page 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Page 115: ...Maintenance 111 R10 and R11 9 10 ...
Page 116: ...112 Maintenance R10 and R11 11 ...
Page 117: ...Maintenance 113 R10 and R11 12b 12a ...
Page 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Page 134: ...130 Technical data ...
Page 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Page 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Page 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Page 140: ...136 Dimension drawings ...
Page 152: ...148 Safe torque off function ...
Page 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...