Note:
•
Consult the motor manufacturer before using a motor with nominal voltage that
differs from the AC line voltage connected to the drive input.
•
The voltage peaks at the motor terminals are relative to the supply voltage of the
drive, not to the drive output voltage.
■
Protecting the motor insulation and bearings
The drive employs modern IGBT inverter technology. Regardless of frequency, the
drive output comprises pulses of approximately the drive DC bus voltage with a very
short rise time. The pulse voltage can almost double at the motor terminals, depending
on the attenuation and reflection properties of the motor cable and the terminals.
This can cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings. This
can gradually erode the bearing races and rolling elements.
d
u/dt filters protect motor insulation system and reduce bearing currents. Common
mode filters mainly reduce bearing currents. Insulated N-end (non-drive end) bearings
protect the motor bearings.
■
Requirements tables
These tables show how to select the motor insulation system and when a drive d
u/dt
and common mode filters and insulated N-end (non-drive end) motor bearings are
required. Ignoring the requirements or improper installation may shorten motor life
or damage the motor bearings and voids the warranty.
Guidelines for planning the electrical installation 75
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...