Start-up
■
Setting the parameters
1.
Power up the drive.
2.
If no warning is shown,
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CAIO-01.
•
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of 15.02 is CAIO-01
•
set the value of parameter 15.01 to CAIO-01.
You can now see the parameters of the extension module in group 15 I/O extension
module.
3.
Set the parameters of analog inputs AI3, AI4, AI5 or analog outputs AO3 or AO4
to applicable values, see the firmware manual.
Example: To connect supervision 1 to AI3 of the extension module:
•
Select the mode of the supervision function (32.05 Supervision function 1).
•
Set limits for the supervision function (32.09 Supervision 1 low and 32.10
Supervision 1 high).
•
Select the supervision action (32.06 Supervision 1 action).
•
Connect 32.07 Supervision 1 signal to 15.52 AI3 scaled value.
Diagnostics
■
LEDs
The adapter module has one diagnostic LED.
Description
Color
The adapter module is powered up.
Green
There is no communication with the drive control unit or the adapter module has
detected an error.
Red
Technical data
Into slot 2 of drive control unit
Installation
IP20 / UL 1 Type
Degree of protection
See the drive technical data.
Ambient conditions
Cardboard
Package
Analog inputs (80..82, 83..85, 86..88)
1.5 mm
2
Maximum wire size
-11 V … +11 V
Input voltage ( AI+ and AI-)
-22 mA … +22 mA
Input current ( AI+ and AI-)
>200 kohm (voltage mode), 100 ohm (current mode)
Input resistance
Optional cable shield connections
Analog outputs (90..92, 93..95)
252 CAIO-01 bipolar analog I/O adapter module
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...