Start-up including validation test
To ensure the safe operation of a safety function, validation is required. The final
assembler of the machine must validate the function by performing a validation test.
The test must be performed
1.
at initial start-up of the safety function
2.
after any changes related to the safety function (circuit boards, wiring,
components, settings, replacement of inverter module, etc.)
3.
after any maintenance work related to the safety function
4.
after a drive firmware update
5.
at the proof test of the safety function.
■
Competence
The validation test of the safety function must be carried out by a competent person
with adequate expertise and knowledge of the safety function as well as functional
safety, as required by IEC 61508-1 clause 6. The test procedures and report must be
documented and signed by this person.
■
Validation test reports
Signed validation test reports must be stored in the logbook of the machine. The
report shall include documentation of start-up activities and test results, references
to failure reports and resolution of failures. Any new validation tests performed due
to changes or maintenance shall be logged into the logbook.
■
Validation test procedure
After wiring the Safe torque off function, validate its operation as follows.
Note: If a CPTC-02 or an FSPS-21 module is installed, refer to its documentation.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the equip-
ment can occur.
Make sure that the motor can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power line
using a disconnector.
Check the STO circuit connections against the wiring diagram.
Close the disconnector and switch the power on.
Test the operation of the STO function when the motor is stopped.
• Give a stop command for the drive (if running) and wait until the motor shaft is at a standstill.
Make sure that the drive operates as follows:
• Open the STO circuit. The drive generates an indication if one is defined for the 'stopped'
state in parameter 31.22 (see the firmware manual).
• Give a start command to verify that the STO function blocks the drive's operation. The motor
should not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
The Safe torque off function 229
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...