Altitude derating
At altitudes above 1000 m (3281 ft) above sea level, the output current derating is 1
percentage point for every added 100 m (328 ft). For example, the derating factor for
1500 m (4921 ft) is 0.95. The maximum permitted installation altitude is given in the
technical data.
If the surrounding air temperature is less than +40 °C (104 °F), the derating can be
reduced by 1.5 percentage points for every 1 °C (1.8 °F) reduction in temperature. A
few altitude derating curves are shown below.
1500 m
1000 m
+25 °C
+30 °C
+77 °F
+86 °F
+40 °C
+104 °F
+35 °C
+95 °F
+20 °C
+68 °F
3300 ft
4921 ft
2000 m
6562 ft
2500 m
8202 ft
3000 m
9842 ft
3500 m
11429 ft
4000 m
13123 ft
1.00
0.95
0.85
0.90
0.80
Derating factor 1.00
Derating factor 0.95
Derating factor 0.90
Derating factor 0.85
Derating factor 0.80
For a more accurate derating, use the DriveSize PC tool.
■
Switching frequency derating
Switching frequencies other than 1.5 kHz can require output current derating. If you
change the minimum switching frequency with parameter 97.02, calculate the derated
output current by multiplying the current given in the rating table by the derating
factor given in the table below. Changing the switching frequency reference with
parameter 97.01 does not require derating.
Derating factor (k) for the minimum switching frequencies
8 kHz
4 kHz
2 kHz
1 kHz
0.58
0.78
0.92
1
Technical data 181
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...