Connected with jumpers at the factory.
6)
Use shielded twisted-pair cables for digital signals.
7)
Ground the outer shield of the cables 360° at the cabinet entry.
8)
WARNING! Connect an external AC power supply (24 V AC) only to control unit connectors
40 and 41. If you connect it to connector AGND, DGND or SGND, damage to the power supply
or control unit can occur.
9)
■
Switches
Position
Description
Switch
Bus not terminated (default)
TERM
ON
EFB link termination. Must be set
to the terminated (ON) position
when the drive (or another
device) is the first or last unit on
the link.
TERM
S4
Bus terminated
TERM
ON
Bias off (default)
BIAS
ON
Switches on the biasing voltages
to the bus. One (and only one)
device, preferably at the end of
the bus must have the bias on.
BIAS
S5
Bias on
BIAS
ON
Additional information on I/O connections
■
PNP configuration for digital inputs (X2 & X3)
Internal and ex24 V power supply connections for PNP configuration are shown
in the figure below.
Ex24 V power supply
PNP connection (source)
X2 & X3
10 +24V
11
DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
+24 V DC
0 V DC
In24 V power supply
PNP connection (source)
X2 & X3
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.
Control unit 139
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...