68 Program features
Torque control performance figures
The drive can perform precise torque control without any speed feedback from the
motor shaft. The table below shows typical performance figures for torque control.
Power loss ride-through
See section
Undervoltage control (power loss ride-through)
U/f
ratio
The
U
/f function is available only in scalar motor control mode, which uses frequency
control.
The function has the following modes:
• Linear
• Squared.
Linear mode
In linear mode, the ratio of voltage to frequency is constant below the field weakening
point. This is used in constant torque applications where it may be necessary to
produce torque at or near the rated torque of the motor throughout the frequency
range
Squared mode
In squared mode, the ratio of the voltage to frequency increases as the square of the
frequency below the field weakening point. This is typically used in centrifugal pump
t
(s)
T
N
= rated motor torque
T
ref
= torque reference
T
act
= actual torque
Torque control
Performance
Non-linearity
± 5% with nominal
torque
(± 20% at the most
demanding operating
point)
Torque step rise time < 10 ms with nominal
torque
100
< 5 ms
90
10
T
ref
T
act
T
T
N
(%)
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...