Fault tracing 425
2381
IGBT overload
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short circuit
in the motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
2392
BU earth leakage
Total earth leakage of inverter
modules is excessive.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Measure insulation resistances of motor
cables and motor.
Contact your local ABB representative.
3130
Input phase loss
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or
blown fuse.
Check input power line fuses.
Check for loose power cable
connections.
Check for input power supply imbalance.
3181
Wiring or earth fault
Programmable fault:
Incorrect input power and
motor cable connection (ie.
input power cable is connected
to drive motor connection).
Check input power connections.
3210
DC link overvoltage
Excessive intermediate circuit
DC voltage.
Check that overvoltage control is on
(parameter
).
Check that the supply voltage matches
the nominal input voltage of the drive.
Check the supply line for static or
transient overvoltage.
Check brake chopper and resistor (if
present).
Check deceleration time.
Use coast-to-stop function (if applicable).
Retrofit drive with brake chopper and
brake resistor.
Check that the brake resistor is
dimensioned properly and the resistance
is between acceptable range for the
drive.
3220
DC link undervoltage
Intermediate circuit DC voltage
is not sufficient because of a
missing supply phase, blown
fuse or fault in the rectifier
bridge. See also section
Check supply cabling, fuses and
switchgear.
3291
BU DC link difference
Difference in DC voltages
between parallel-connected
inverter modules.
Check the auxiliary code (format XXXY
YYZZ). “XXX” specifies the source of the
first error (see “YYY”). “YYY” specifies
the module through which BCU control
unit channel the fault was received (
1
:
Channel 1,
2
: Channel 2,
4
: Channel 3,
8
:
Channel 4, …,
800:
Channel 12).
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...