ACS510 User’s Manual
51
Start-Up
Macro Default Values for Parameters
Parameter default values are listed in "Complete Parameter List for ACS510".
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
ACS510-01
* This parameter is not available in software N688 and +N689.
Parameter
ABB
St
an
d
ar
d
3-w
ir
e
Alternate
Motor
Potentiometer
Hand-auto
PID Control
PFC Control
SPFC Control
9902
APPLIC
MACRO
1
2
3
4
5
6
7
15
1001
EXT
1
COMMANDS
2
4
9
2
2
1
1
1
1002
EXT
2
COMMANDS
0
0
0
0
7
6
6
6
1003
*
DIRECTION
3
3
3
3
3
1
1
1
1102
EXT
1/
EXT
2
SEL
0
0
0
0
3
2
3
3
1103
REF
1
SELECT
1
1
1
12
1
1
1
1
1106
REF
2
SELECT
2
2
2
2
2
19
19
19
1201
CONST
SPEED
SEL
9
10
9
5
0
9
0
0
1304
MINIMUM
AI
2
0
0
0
0
20
20
20
20
1401
RELAY
OUTPUT
1
1
1
1
1
1
1
2
2
1402
RELAY
OUTPUT
2
2
2
2
2
2
2
3
31
1403
RELAY
OUTPUT
3
3
3
3
3
3
3
31
31
1501
AO
1
CONTENT
SEL
103
102
102
102
102
102
103
103
1503
AO
1
CONTENT
MAX
50
50
50
50
50
50
52
52
1507
AO
2
CONTENT
SEL
104
104
104
104
104
104
130
130
1510
MINIMUM
AO
2
0
0
0
0
0
0
4
4
1601
RUN
ENABLE
0
0
6
6
4
5
2
2
2008
MAXIMUM
FREQ
50
50
50
50
50
50
52
52
2201
ACC
/
DEC
1/2
SEL
5
0
5
0
0
0
0
0
3201
SUPERV
1
PARAM
103
102
102
102
102
102
103
103
3401
SIGNAL
1
PARAM
103
102
102
102
102
102
103
103
4001
GAIN
2.5
2.5
2.5
2.5
2.5
2.5
25
2.5
4002
INTEGRATION
TIME
3
3
3
3
3
3
3
3
4101
GAIN
1
1
1
1
1
1
2,5
2.5
4102
INTEGRATION
TIME
60
60
60
60
60
60
3
3
8118
AUTOCHG
INTERV
0
0
0
0
0
0
0
0.1
8123
PFC
ENABLE
0
0
0
0
0
0
1
2