Diagnostics
Fault Resetting
The ACS510 can be configured to automatically reset certain faults. Refer to
parameter Group 31: Automatic Reset.
Warning!
If an external source for start command is selected and it is active, the
ACS510 may start immediately after fault reset.
Flashing Red LED
To reset the drive for faults indicated by a flashing red LED:
• Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
• From the control panel: Press RESET
• Turn the power off for 5 minutes.
1006
PAR
EXT
RO
Parameter values are inconsistent. Check for the following:
• Extension relay module not connected and
• 1410…1412
RELAY
OUTPUTS
4…6 have non-zero values.
1007
PAR
FIELDBUS
MISSING
Parameter values are inconsistent. Check for and correct:
• A parameter is set for fieldbus control (e.g. 1001
EXT
1
COMMANDS
= 10
(
COMM
)), but 9802
COMM
PROT
SEL
= 0.
1008
REVERSED
1009
PAR
PCU
1
Parameter values for power control are inconsistent: Improper motor
nominal frequency or speed. Check for both of the following:
• 1 < (60 * 9907
MOTOR
NOM
FREQ
/ 9908
MOTOR
NOM
SPEED
< 16
• 0.8 < 9908
MOTOR
NOM
SPEED
/
(120 * 9907
MOTOR
NOM
FREQ
/ Motor Poles) < 0.992
1011
PAR
OVERRIDE
See Parameter Group 17.
1012
PAR
PFC
IO
1
IO configuration is not complete – not enough relays are parameterized to
PFC. Or, a conflict exists between Group 14, parameter 8117,
NR
OF
AUX
MOT
, and parameter 8118,
AUTOCHNG
INTERV
.
1013
PAR
PFC
IO
2
IO configuration is not complete – the actual number of PFC motors
(parameter 8127,
MOTORS
) does not match the PFC motors in Group 14
and parameter 8118
AUTOCHNG
INTERV
.
1014
PAR
PFC
IO
3
IO configuration is not complete – the drive is unable to allocate a digital
input (interlock) for each PFC motor (parameters 8120
INTERLOCKS
and
8127
MOTORS
).
1015
PAR
USER
DEFINED
U
/
F
The user defined U/f ratio is not compatibility (only when parameters 2605
= 3 ).
1016
PAR
USER LOAD
C
See Parameter Group 37.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action