ACS510 User’s Manual
Installation
macro. See "Application Macros" on page 42.
Note!
Terminals 3, 6, and 9 are at the same potential.
Note!
For safety reasons the fault relay signals a “fault” when the ACS510 is
powered down.
You can wire the digital input terminals in either a PNP or NPN configuration.
Install the Wiring
Checking Motor and Motor Cable Insulation
Warning!
Check the motor and motor cable insulation before connecting the drive to
input power. For this test, make sure that motor cables are NOT connected to the
drive.
1. Complete motor cable connections to the motor, but NOT to the drive output
terminals (U2, V2, W2).
2. At the drive end of the motor cable, measure the insulation
resistance between each motor cable phase and Protective
Earth (PE): Apply a voltage of 1 kV DC and verify that
resistance is greater than 1 Mohm.
NPN connection (sink)
PNP connection (source)
10 +24 V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
10 +24 V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
X1
X1
PE
M
ohm