1.
Stop the drive and do the steps in section
Electrical safety precautions (page 14)
before
you start the work.
2.
Make sure that the resistor cable is connected to the resistor and disconnected from
the drive output terminals.
3.
At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the conductors and the PE conductor with
a measuring voltage of 1000 V DC. The insulation resistance must be higher than
1 Mohm.
R-
R+
ohm
PE
1 kV DC,
> 1 Mohm
Earthing system compatibility check – North America
This section is valid for the UL(NEC) drive types. For the IEC drives types, see
system compatibility check – IEC (page 53)
■
EMC filter
The drive has an internal EMC filter as standard. However, for the UL(NEC) drive types,
the filter is disconnected as default. The filter is typically not needed in North American
installations.
If you are concerned with EMC issues, and install the drive to a symmetrically grounded
TN-S system, you can connect the internal EMC filter. See
varistor, or connecting EMC filter
Note:
When the internal EMC filter is disconnected, the electromagnetic compatibility of the
drive is reduced.
■
Ground-to-phase varistor
The drive is equipped with an internal ground-to-phase varistor as standard. For frame sizes
R1, R3 and R4, the varistor is connected as default. For frame size R2, the varistor is
disconnected as default.
A drive with the ground-to-phase varistor connected can be installed to a symmetrically
grounded TN-S system. If you install the drive to another system, you may need to disconnect
the varistor. See
When to disconnect ground-to-phase varistor, or connect EMC filter
.
■
When to disconnect ground-to-phase varistor, or connect EMC filter
The table below shows different earthing systems, and when to disconnect ground-to-phase
varistor, or connect EMC filter, ie, maintain or remove the factory default EMC screw or VAR
screw.
Electrical installation – North America 71
11
Summary of Contents for ACS480
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 24: ...24 ...
Page 34: ...34 ...
Page 122: ...122 ...
Page 124: ...Frame R1 Frame R1 front side IP20 UL type open 124 Dimension drawings ...
Page 125: ... Frame R1 bottom rear IP20 UL type open Dimension drawings 125 ...
Page 126: ... Frame R1 front side UL type 1 kit installed 126 Dimension drawings ...
Page 127: ... Frame R1 bottom rear UL type 1 kit installed Dimension drawings 127 ...
Page 128: ...Frame R2 Frame R2 front side IP20 UL type open 128 Dimension drawings ...
Page 129: ... Frame R2 bottom rear IP20 UL type open Dimension drawings 129 ...
Page 130: ... Frame R2 front side UL type 1 kit installed 130 Dimension drawings ...
Page 131: ... Frame R2 bottom rear UL type 1 kit installed Dimension drawings 131 ...
Page 132: ...Frame R3 Frame R3 front side IP20 UL type open 132 Dimension drawings ...
Page 133: ... Frame R3 bottom rear IP20 UL type open Dimension drawings 133 ...
Page 134: ... Frame R3 front side UL type 1 kit installed 134 Dimension drawings ...
Page 135: ... Frame R3 bottom rear UL type 1 kit installed Dimension drawings 135 ...
Page 136: ...Frame R4 Frame R4 front side IP20 UL type open 136 Dimension drawings ...
Page 137: ... Frame R4 bottom rear IP20 UL type open Dimension drawings 137 ...
Page 138: ... Frame R4 front side UL type 1 kit installed 138 Dimension drawings ...
Page 139: ... Frame R4 bottom rear UL type 1 kit installed Dimension drawings 139 ...
Page 140: ...140 ...
Page 163: ... Declaration of conformity The Safe torque off function 163 ...
Page 164: ...164 ...
Page 172: ...Dimensions 172 BIO 01 I O extension module ...
Page 178: ...178 ...