Resistor braking 135
Protecting the system in brake circuit fault situations
Protecting the system in cable and brake resistor short-circuit
situations
The input fuses will also protect the resistor cable when it is identical with the input
cable.
Protecting the system against thermal overload
Equipping the drive with a main contactor is highly recommended for safety reasons.
Wire the contactor so that it opens in case the resistor overheats. This is essential for
safety since the drive will not otherwise be able to interrupt the main supply if the
chopper remains conductive in a fault situation. An example wiring diagram is shown
below. ABB recommends that you use resistors equipped with a thermal switch (1)
inside the resistor assembly. The switch indicates overtemperature and overload.
ABB recommends that you also wire the thermal switch to a digital input of the drive.
Mechanical installation
Refer to the resistor manufacturer’s instructions.
Drive
L1 L2 L3
1
2
3
4
5
6
13
14
3
4
1
2
K1
OFF
ON
L1 L2 L3
1
Drive
10
+24V
x
DIx
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...