58 Actual signals and parameters
6021
PMP CLEAN
SELECT
Enables the pump cleaning sequence for the inverter
in the manual mode (see
and defines the selection conditions.
WARNING!
Before enabling the pump
cleaning sequence, make sure that it can be
performed safely with the connected
equipment.
Note
: When the pump cleaning sequence is active, it
cannot be stopped with OFF selection. After the
cleaning sequence is completed successfully or if the
sequence is interrupted due to a fault, it automatically
switches to OFF selection.
OFF
OFF
Disables pump cleaning sequence.
0
ON
Enables pump cleaning sequence.
1
6022
PMP CLEAN
SPEED
Defines the speed at which the pump cleaning
sequence is initiated.
1 = 1 rpm
500...3000
Speed.
500 rpm
6023
PMP CLEAN
TIME
Defines the pump cleaning time for which the motor
rotates in one direction (forward or reverse) within
which the cleaning sequences are counted.
1 = 1 sec
1...300
Time
60 sec
61 FLOW
CALCULATION
Defines flow calculation parameters.
6101
PQ CURVE P1
Defines the input power of pump in kW at point 1 on
the PQ performance curve.
For description of PQ curve, see section
, page
.
10 = 1 kW
All parameters
No.
Name/
Value
Description
Def/ FbEq
Q[m³/h]
6105
6101
6111
6115
P[kW]
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives Supplement ACS355 Solar pump inverter N827...
Page 4: ......
Page 10: ...10 Safety...
Page 14: ...14 Introduction...
Page 18: ...18 Operating principle and hardware description...
Page 30: ...30 Start up and controls...
Page 36: ...36 Program features...
Page 66: ...66 Actual signals and parameters...
Page 70: ...70 Fault tracing...
Page 76: ...76 Technical data...