Application macros
90
Motor Potentiometer macro
This macro provides a cost-effective interface for PLCs that vary the speed of the
drive using only digital signals. To enable the macro, set the value of parameter
to 4 (MOTOR POT).
For the parameter default values, see section
Default values with different macros
. If you use other than the default connections presented below, see
section
.
Default I/O connections
max. 500 ohm
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Not in use by default: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 VDC, max. 10 mA
5
AI2
Not in use by default. 0…10 V
6
GND
Analog input circuit common
7
AO
Motor speed value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 VDC, max. 200 mA
10
GND
Auxiliary voltage output common
11
DCOM
Digital input common
12
DI1
Stop (0) / Start (1)
13
DI2
Forward (0) / Reverse (1)
14
DI3
Speed reference up
1)
15
DI4
Speed reference down
1)
16
DI5
Constant speed 1
X1B
17
ROCOM
Relay output
No fault [Fault (-1)]
18
RONC
19
RONO
20
DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21
DOOUT
22
DOGND
2)
1)
If DI3 and DI4 are both active or inactive, the
speed reference is unchanged.
The existing speed reference is stored during
stop and power down.
2)
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...