I/O Settings mode
In the I/O Settings mode, you can:
• check the parameter settings related to any I/O terminal
• edit the parameter setting. For example, if “1103: REF1” is listed under Ain1
(Analog input 1), that is, parameter
REF1 SELECT has value AI1, you can
change its value to e.g. AI2. You cannot, however, set the value of parameter
REF2 SELECT to AI1.
• start, stop, change the direction and switch between local and remote control.
How to edit and change parameter settings related to I/O terminals
Step
Action
Display
1.
Go to the Main menu by pressing
if you are in the Output mode, otherwise
by pressing
repeatedly until you get to the Main menu.
2.
Go the I/O Settings mode by selecting I/O SETTINGS on the menu with keys
and
, and pressing
.
3.
Select the I/O group, e.g. DIGITAL INPUTS, with keys
and
, and
press
. After a brief pause, the display shows the current settings for the
selection.
4.
Select the setting (line with a parameter number) with keys
and
,
and press
.
5.
Specify a new value for the setting with keys
and
.
Pressing the key once increments or decrements the value. Holding the key
down changes the value faster. Pressing the keys simultaneously replaces the
displayed value with the default value.
6.
• To save the new value, press
.
• To cancel the new value and keep the original, press
.
MENU
EXIT
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT
ENTER
00:00
MAIN MENU
1
LOC
ENTER
DIGITAL INPUTS (DI)
ANALOG INPUTS (AI)
RELAY OUTPUTS (ROUT)
ANALOG OUTPUTS (AOUT)
PANEL
EXIT
SEL
00:00
I/O SETTINGS
1
LOC
SEL
—DI1—
1001:START/STOP (E1)
—DI2—
—DI3—
SHOW I/O
1
LOC
EXIT
00:00
EDIT
1001 EXT1 COMMANDS
PAR EDIT
DI1
CANCEL
SAVE
00:00
[1]
LOC
1001 EXT1 COMMANDS
PAR EDIT
DI1,2
CANCEL
SAVE
00:00
[2]
LOC
SAVE
CANCEL
—DI1—
1001:START/STOP (E1)
—DI2—
1001:DIR (E1)
—DI3—
EXIT
00:00
SHOW I/O
1
LOC
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......