Control panels
75
How to select the monitored signals
Step
Action
Display
1.
You can select which signals are monitored in the Output mode and how they
are displayed with group
parameters. See page
for
detailed instructions on changing parameter values.
By default, the display shows three signals. The particular default signals
depend on the value of parameter
APPLIC MACRO: For macros whose
default value of parameter
MOTOR CTRL MODE is 1 (VECTOR:SPEED),
the default for signal 1 is
SPEED, otherwise
defaults for signals 2 and 3 are always
CURRENT and
TORQUE,
respectively.
To change the default signals, select up to three signals from group
Signal 1: Change the value of parameter
SIGNAL1 PARAM to the index of
the signal parameter in group
(= number of the
parameter without the leading zero), e.g. 105 means parameter
TORQUE.
Value 0 means that no signal is displayed.
Repeat for signals 2 (
SIGNAL3 PARAM).
2.
Select how you want the signals to be displayed: as a decimal number or a bar
graph. For decimal numbers, you can specify the decimal point location, or use
the decimal point location and unit of the source signal [setting (9 (DIRECT)].
For details, see parameter
.
Signal 1: parameter
OUTPUT1 DSP FORM
Signal 2: parameter
OUTPUT2 DSP FORM
Signal 3: parameter
OUTPUT3 DSP FORM.
3.
Select the units to be displayed for the signals. This has no effect if parameter
is set to 9 (DIRECT). For details, see parameter
Signal 1: parameter
Signal 2: parameter
Signal 3: parameter
4.
Select the scalings for the signals by specifying the minimum and maximum
display values. This has no effect if parameter
/
is set to 9
(DIRECT). For details, see parameters
and
OUTPUT1 MIN and
OUTPUT1 MAX
OUTPUT2 MIN and
OUTPUT2 MAX
OUTPUT3 MIN and
OUTPUT3 MAX.
3401 SIGNAL1 PARAM
PAR EDIT
OUTPUT FREQ
CANCEL
SAVE
00:00
[103]
LOC
3408 SIGNAL2 PARAM
PAR EDIT
CURRENT
CANCEL
SAVE
00:00
[104]
LOC
3415 SIGNAL3 PARAM
PAR EDIT
TORQUE
CANCEL
SAVE
00:00
[105]
LOC
3404 OUTPUT1 DSP FORM
PAR EDIT
DIRECT
CANCEL
SAVE
00:00
[9]
LOC
3405 OUTPUT1 UNIT
PAR EDIT
Hz
CANCEL
SAVE
00:00
[3]
LOC
3406 OUTPUT1 MIN
PAR EDIT
0.0 Hz
CANCEL
SAVE
00:00
LOC
3407 OUTPUT1 MAX
PAR EDIT
500.0 Hz
CANCEL
SAVE
00:00
LOC
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......