Start-up, control with I/O and ID Run
46
How to perform the limited start-up
For the limited start-up, you can use the Basic Control Panel or the Assistant Control
Panel. The instructions below are valid for both control panels, but the displays
shown are the Basic Control Panel displays, unless the instruction applies to the
Assistant Control Panel only.
Before you start, ensure that you have the motor nameplate data on hand.
POWER-UP
Apply input power and wait for a moment.
Check that the red LED is not lit and the green LED is lit but not blinking.
The drive is now ready for use.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
must be followed during the start-up
procedure.
The drive will start up automatically at power up if the external run command is on.
Check the installation. See the checklist in chapter
.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine
if:
• there is a risk of damage in case of incorrect direction of rotation, or
• an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
POWER-UP
Apply input power.
The Basic Control Panel powers up into the Output mode.
The Assistant Control Panel asks if you want to run the Start-
up Assistant. If you press
, the Start-up Assistant is not
run, and you can continue with manual start-up in a similar
manner as described below for the Basic Control Panel.
REM
Hz
OUTPUT FWD
00
.
EXIT
Do you want to
use the start-up
assistant?
Yes
No
EXIT
OK
00:00
CHOICE
REM
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......